As a rule of thumb, a genset continuous power rating should not be less than 1.5 times the UPS nominal power. The oversizing factor accounts for UPS efficiency, typically 96%, UPS power factor, typically 0.99, input harmonic distortion, typically 3% and adds up a power safety margin to prevent load steps from triggering a non-stable response in the genset’s output voltage. As mentioned above, thou...