AC electrical loads are referred to either as linear or non linear load depending on how they draw current from the mains power supply waveform.
Linear Load
UPS loads where the voltage and current waveforms are sinusoidal. The current at any time is proportional to voltage.
Non Linear Load
Foremost among loads meeting their definition are gas discharge lighting having saturated ballast coils and thyritor (SCR) controlled loads.
Difference Between Linear load and Non Linear Load
Effects of Harmonics on Neutral
In a 4-wire three phase system, the fundamental currents at any instant will always add up to zero in the neutral. However, the third harmonic of each phase is always in phase with those of the other two phases. As a result, rather than canceling each other (as is the case with the fundamental), they are additive and may well lead to serious neutral loading problems. As an example: a three phase system has 100 amperes load and each phase contains 30% third harmonic. The harmonic current flowing through the neutral will be three times. 30% of 100, or 90 amperes at the three times of the fundamental frequency (150 Hz for 50 Hz systems).
Therefore, it is recommended to use neutral of minimum double the capacity since total load on the system in consideration of Linear loads and Non Linear loads. It is also advised to use single phase UPS/Loads wherever possible with individual neutral in place of using three phase UPS/Loads.
tags :
recent posts
scan to wechat:everexceed